Notifier XP10-M(A) Ten Input Monitor Module (NEW)
Notifier XP10-MA Ten-Input Monitor Module
The Notifier XP10-MA is an intelligent, addressable ten-input monitor module designed to interface between a fire alarm control panel and normally open contact devices such as pull stations, water flow switches, and other initiating devices. Engineered for reliability and seamless system integration, this module allows independent supervision and status monitoring of up to ten circuits, making it an ideal solution for large-scale fire alarm installations.
Key Features:
- Monitors Ten Independent Circuits – Each input is individually supervised and reports status changes to the control panel.
- Addressable Device – Uses rotary address switches for precise identification within the system.
- Removable Plug-in Terminal Blocks – Simplifies installation and maintenance.
- LED Status Indicators – Each input has a dedicated LED indicator for quick visual diagnostics.
- Supports Class A & Class B Wiring – Offers flexible wiring configurations based on system requirements.
- Compatible with FlashScan® & CLIP Protocols – Ensures stable communication with Notifier intelligent fire alarm panels.
- Space-Efficient Design – Can be mounted in Notifier BB-XP cabinets or CHS-6 chassis for compact installations.
Technical Specifications:
- Operating Voltage: 15–32 VDC
- Standby Current: 3.5 mA
- Alarm Current: 55 mA (with all ten LEDs lit)
- Temperature Range: 32°F to 120°F (0°C to 49°C)
- Humidity Range: 10% to 93% non-condensing
- Max IDC Wiring Resistance: 1,500 ohms
- Max IDC Voltage: 10.2 VDC
- Max IDC Current: 240 µA (per device)
- Dimensions: 6.8" H x 5.8" W x 1.25" D