Edwards 3-FTCU Firefighter's Telephone Control Unit (NEW)

Edwards 3-FTCU Firefighter's Telephone Control Unit (NEW)

  • $2,100.00


The 3-FTCU Firefighter's Telephone Control Unit (FTCU) is designed to used in conjunction with the 3-ASU Audio Source Unit (ASU), mounted on a common chassis. The two units in combination provide the main telephone riser, the Audio Source Unit with Firefighter's Telephone (ASU/FT). The telephone circuit requires a separate hardwired riser and is not multiplexed over the network audio riser. The riser is supervised by the URSM. The ASU/FT requires one chassis space within an enclosure. The 3-FTCU features the following switches: Connect (link incoming to master headset), Review Pending (scroll through incoming pending calls), Acknowledge (silence in-call buzzer), Disconnect (remove a connected phone from system), and Review Connected (scroll through active connected calls). 

Key Features

  • Prerecorded Message Storage – Standard 2-minute capacity, expandable up to 100 minutes for enhanced emergency communication.

  • Reliable Telephone Riser – Supports up to 5 active firefighter telephones with Class A/B configuration and supervised EOL resistor (15 kΩ).

  • Durable & Efficient Wiring – Uses 1-2 pair twisted-shielded 18 AWG wiring with a maximum line impedance of 52 Ω, 0.2 μF.

  • Secure Termination – Includes modular phone jack for message downloads and dedicated plug-in terminals for microphones and firefighter telephones.

  • Rugged Operating Conditions – Designed to perform in temperatures from 32°F to 120°F (0°C to 49°C) with up to 93% non-condensing humidity.

 

DATASHEET